Free download
Free legionella logbook template
- City & Guilds WH004 qualified assessors
- Legionella Control Association registered
- UKAS accredited laboratories
- Works to HSE ACoP L8 and HSG 274
Your legionella logbook
Use the checks and intervals your own risk assessment sets. These are the usual ones.
Site details
- Site name and address
- Responsible person
- Risk assessment date
- Risk assessment carried out by
- Next review date
- Emergency contact
Monthly temperature checks
Hot: at least 50°C within one minute (55°C in healthcare premises). Cold: below 20°C. Check the nearest and furthest outlets from the cylinder or tank.
| Date | Outlet and location | Hot °C | Cold °C | OK? | Action taken | Initials |
|---|---|---|---|---|---|---|
Hot water cylinder checks
Stored hot water: at least 60°C.
| Date | Cylinder | Flow °C | Return °C | OK? | Action taken | Initials |
|---|---|---|---|---|---|---|
Weekly flushing of little-used outlets
Outlets that are not used at least once a week should be flushed.
| Date | Outlet and location | Flushed for (minutes) | Initials |
|---|---|---|---|
Shower cleaning and descaling
Showerheads and hoses: usually every three months.
| Date | Shower and location | Cleaned and descaled | Disinfected | Initials |
|---|---|---|---|---|
Cold water tank inspections
Check the lid, the insulation, the screen on the overflow, and for debris or stagnation.
| Date | Tank and location | Condition | Temperature °C | Action taken | Initials |
|---|---|---|---|---|---|
Samples, faults and work done
Record every water sample and its result, and any repair or disinfection.
| Date | What was done or found | By whom | Result | Follow-up |
|---|---|---|---|---|
Free template from Legionella Testing, legionellatesting.co.uk. The limits shown are from HSE guidance. A logbook records the checks your risk assessment sets; it does not replace the assessment.
Rather have it done for you?
We carry out the monthly checks, the quarterly shower cleaning and the tank inspections, and keep your logbook up to date.
Legionella logbook: common questions
What should a legionella logbook contain?
Who is responsible, the risk assessment and control scheme, and the result and date of every check: temperatures, flushing, shower cleaning, tank inspections, any samples and any work done.
How long should legionella records be kept?
HSE says monitoring records should be kept for at least five years, and the risk assessment and control scheme for at least two years after they are replaced.
Is a logbook enough to comply?
No. A logbook records the checks your risk assessment sets. Without the risk assessment you do not know which checks your building needs.
Source: HSE: Monitoring and keeping records. Checked 14 November 2026.
Legionella risk assessments from £200 + VAT
Free, fixed quote within 24 hours. No obligation.