Skip to content
Legionella Testing

Free download

Free legionella logbook template

Record sheets for the routine checks that keep a hot and cold water system under control. Print them, or save them as a PDF, and keep them with your risk assessment.
  • City & Guilds WH004 qualified assessors
  • Legionella Control Association registered
  • UKAS accredited laboratories
  • Works to HSE ACoP L8 and HSG 274

Your legionella logbook

Use the checks and intervals your own risk assessment sets. These are the usual ones.

Site details

Site name and address
Responsible person
Risk assessment date
Risk assessment carried out by
Next review date
Emergency contact

Monthly temperature checks

Hot: at least 50°C within one minute (55°C in healthcare premises). Cold: below 20°C. Check the nearest and furthest outlets from the cylinder or tank.

DateOutlet and locationHot °CCold °COK?Action takenInitials

Hot water cylinder checks

Stored hot water: at least 60°C.

DateCylinderFlow °CReturn °COK?Action takenInitials

Weekly flushing of little-used outlets

Outlets that are not used at least once a week should be flushed.

DateOutlet and locationFlushed for (minutes)Initials

Shower cleaning and descaling

Showerheads and hoses: usually every three months.

DateShower and locationCleaned and descaledDisinfectedInitials

Cold water tank inspections

Check the lid, the insulation, the screen on the overflow, and for debris or stagnation.

DateTank and locationConditionTemperature °CAction takenInitials

Samples, faults and work done

Record every water sample and its result, and any repair or disinfection.

DateWhat was done or foundBy whomResultFollow-up

Free template from Legionella Testing, legionellatesting.co.uk. The limits shown are from HSE guidance. A logbook records the checks your risk assessment sets; it does not replace the assessment.

Rather have it done for you?

We carry out the monthly checks, the quarterly shower cleaning and the tank inspections, and keep your logbook up to date.

Legionella logbook: common questions

What should a legionella logbook contain?

Who is responsible, the risk assessment and control scheme, and the result and date of every check: temperatures, flushing, shower cleaning, tank inspections, any samples and any work done.

How long should legionella records be kept?

HSE says monitoring records should be kept for at least five years, and the risk assessment and control scheme for at least two years after they are replaced.

Is a logbook enough to comply?

No. A logbook records the checks your risk assessment sets. Without the risk assessment you do not know which checks your building needs.

Source: HSE: Monitoring and keeping records. Checked 14 November 2026.

Legionella risk assessments from £200 + VAT

Free, fixed quote within 24 hours. No obligation.